  • 37kW Unenclosed Star Delta Motor Starter
    37kW Unenclosed Star Delta Motor Starter 37kW Unenclosed Star Delta Motor Starter

37kW Unenclosed Star Delta Motor Starter

28 Views

  • Product Code: Unenclosed Star Delta Motor Starter
  • 2 Available
  • $762.00

  • Ex Tax: $692.73

Shipping Estimate

Country:
Region / State:
Post Code:

37kW Unenclosed Star Delta Motor Starter.

415V AC Control Coil.

Overload Included.

 

This star-delta reduced voltage starter is suitable for starting the motor in the circuit of AC 50/60 Hz, voltage up to 660V and maximum motor current up to 69A

 

The start delta unit is provided with a timer for automatic changeover of star delta to reduce the voltage and current of motor starting plus a thermal overload for motor protection.

 

The QJX2 series star delta units use the CJX2 series contactors. The CJX2 series contactors are the old Telemecanique LAD style contactors

 

The default overload supplied with the 37kW star delta unit is TO-40(30-40A).

The maximum motor current specified in the table (see gallery) is a guide please whenever possible, determine the actual full load current from the motor rating plate in each case.

The Star-Delta starters come standard with 415V AC control coil; the units can be fitted with 240V,110V,48V and 24V AC coils. Allow 1-2 working days for the coils to modified.

 

 

Note:

1: Set the overload to 58% of the motor rated current.

2: Always check the full load current of the motor before finalising your selection the maximum load current can vary between motors depending on the efficiency of the motors.